Circuit Breaker Sizing Calculator — MCB Rating Guide
Determine the correct MCB rating and type for your circuit based on BS 7671 18th Edition. Covers all common UK domestic circuit types.
Select the type of circuit being protected
Enter the total load on this circuit
How We Calculate This
This calculator determines the correct Miniature Circuit Breaker (MCB) rating for your circuit based on BS 7671 18th Edition wiring regulations. The MCB must be sized to protect the cable while being large enough to carry the design current without nuisance tripping.
The sizing rule
Ib ≤ In ≤ Iz
Where Ib = design current, In = MCB rating, Iz = cable current carrying capacity.
MCB types explained
- Type B: Trips at 3-5x rated current. Standard for domestic installations (lighting, sockets, showers, cookers).
- Type C: Trips at 5-10x rated current. For moderate inrush loads (some commercial, fluorescent lighting circuits).
- Type D: Trips at 10-20x rated current. For heavy inductive loads (large motors, transformers, welding equipment).
Standard UK MCB ratings
Available ratings: 6A, 10A, 16A, 20A, 32A, 40A, 45A, 50A. The calculator selects the smallest standard MCB rating that is equal to or greater than the load current, then cross-references with typical configurations per BS 7671 for the selected circuit type.
Frequently Asked Questions
Related Calculators
Cable Sizing Calculator
Calculate the correct cable size based on BS 7671 18th Edition regulations.
Voltage Drop Calculator
Check voltage drop complies with UK wiring regulations.
Maximum Demand Calculator
Calculate maximum electrical demand for domestic installations.
Socket Spacing Calculator
Plan socket layouts with Part P guidance on spacing and positioning.
Lighting Layout Calculator
Calculate lighting requirements based on lux levels for each room type.